Data Sheet for Product

4
Siemens CM1N4561en
Smart Infrastructure 2021-06-21
Electronics
SKD60
1)
1 Connection terminals
2 DIL switches
3 LED status indication
4 Stroke calibration
1)
From version ..L onward
DIL switches
Direction of operation Fail-in-place (behaviour in
case of control signal loss)
**
Positioning signal Y
Positioning feedback U
Flow characteristic
ON Reverse acting Stops at current
position
DC 4...20 mA lin = linear
OFF * Direct acting Closes DC 0...10 V log = equal
percentage
Relationship between
positioning signal Y and
volumetric flow
* Factory setting: all switches OFF
** Only considered when DIL switch 3 ON
(control signal = DC 4…20 mA)
SKD60
2)
, SKD62..
1 Connection terminals
2 DIL switches
3 LED status indication
4 Stroke calibration
2)
Up to and including version ..K