Data Sheet for Product

5
Siemens CM1N4561en
Smart Infrastructure 2021-06-21
DIL switches
Positioning signal Y
Positioning feedback U
Flow characteristic
ON DC 4...20 mA lin = linear
OFF * DC 0...10 V log = equal percentage
Relationship between
positioning signal Y and
volumetric flow
* Factory setting: all switches OFF
SKD62UA
1 Connection terminals
2 DIL switches
3 LED status indication
4 Stroke calibration
5 Rotary switch UP
(factory setting 0)
6 Rotary switch LO
DIL switches
Direction of operation Sequence control or stroke
limit control
Positioning signal Y
Positioning feedback U
Flow characteristic
ON Reverse acting Sequence control
Signal addition
QAF21../QAF61..
DC 4...20 mA lin = linear
OFF * Direct acting Stroke limit control DC 0...10 V log = equal
percentage
Relationship between
positioning signal Y and
volumetric flow
* Factory setting: all switches OFF