The LED on the SKD62/MO cable adapter flashes red during the calibration, as the
positioning signal Y and the positioning feedback U do not correspond anymore. This is
interpreted as a blockage and thus indicated as an error.
If necessary, the calibration can be repeated any number of times.
LED indication of operational status
SKD60, SKD62.., SKD62/MO
The dual-colored LED indicating the operational status is visible when the cover is removed.
LED
indication
Function Remarks, troubleshooting
Lit green
Normal operation Automatic operation; everything o.k.
Flashing green
Stroke calibration in progress Wait until calibration is finished
(LED stops flashing, will be lit green or red)
Lit red
Faulty stroke calibration Check mounting; restart stroke calibration (by short-circuiting
calibration slot)
Internal error Replace electronics
Flashing red
Inner valve jammed Troubleshoot, check valve, restart stroke calibration
Dark
No power supply Check mains network, check wiring
Electronics faulty Replace electronics
As a general rule, the LED can only assume the states shown above – continuously lit red or
green, flashing red or green, or off/dark.