Override control Z
SKD60, SKD62..
D The override control input Z can be operated in the following modes of operation:
Z-mdoe
No function Fully open Closed Override with
0…1000 Ω
Signal addition
SKD62UA only
Connections
Transfer
Equal percentage or
linear
Equal percentage or linear
Z-contact not
connected
Z-contact directly
connected to G
Z-contact directly
connected to G0
Z-contact connected
to M via resistor R
Starting position at
50 Ω
End position at
900 Ω
Z-contact
connected to R of
frost protection
monitor QAF21.. or
QAF61..
Valve stroke follows
Y-input
Y-input has no effect Valve stroke follows
Y and R(Z) signal
Shown operation modes are based on the factory setting “direct acting”.
Y-input has no effect in Z-mode.
Selection of direction of operation
SKD60 (from version ..L), SKD62UA
With normally-closed valves, “direct acting” means that with a signal input of 0 V, the
valve closes (applies to all Siemens valves listed under Equipment combinations [ 12]).
With normally-open valves, “direct acting” means that with a signal input of 0 V, the valve
is open.
Direct acting Reverse acting Stroke
Input DC 0...10 V
DC 4...20 mA
0...1000 Ω
Input DC 0...10 V
DC 4...20 mA
0...1000 Ω
The mechanical spring-return function is not affected by the direction of operation selected.