Product Overview
Formed as the `SL-series, Siemens is now offering horns, strobes, and horn-strobes
with LED based strobes to its notification-appliances portfolio.
With the `SL-series, Siemens now offers an additional range of products with low
and high candela settings that makes these sophisticated notification appliances
ideal for new installs and retrofit applications.
Innovative light-emitting diode (LED) strobe technology provides an energy-efficient
means for a significantly reduced current draw.
The strobe portion of these appliances meets the 20 millisecond light-pulse-duration
requirements of the 2016 edition of NFPA 72. This feature allows existing Xenon and
the new LED devices to be used in the same field-of-view.
In a single device, the `SL-series can provide alarm-signaling tones for dual
applications. All strobe models in the series feature multi-candela settings (15 | 30 |
75 | 95cd) on a single appliance.
Additionally, there are two (2) modes of operation for the audible portion of these
notification appliances:
T3 (coded)
Continuous
The `SL-series of horns, strobes and horn-strobes devices are produced in a sleek,
modern design. Its structure and design provide high-quality energy efficiency in an
aesthetically pleasing, low-profile design that is consistent to the look of the interior
composition of the building application.
This `SL-series is exclusive to indoor ceiling-mount applications. The Model `SLHC’-
series horn appliances work in either 12V or 24VDC, whereas the Series `SLSC’ and
`SLHSC’ strobe and horn-strobe devices are specifically for 24V operation.
Notification Appliances
`SLSeries Horns | Strobes | Horn-Strobes
Applications : Indoor, Ceiling-Only
Model SLHSCR-F+
Horn-strobe
Architect & Engineer Specifications
Sophisticated series of notification
appliances that meets fire-industry
codes and regulations for
commercial-building applications
Compatible with the Siemens 50-point,
252-point and 504-point addressable fire
alarm control panels (FACPs), and with:
- Siemens Modular FACPs
- Siemens PAD-series of NAC extenders
- FireFinder® XLS / XLSV FACPs
- Siemens dual-sync control (DSC) modules
Innovative LED strobe technology
provides an energy-efficient means
for a significantly reduced current
draw
- Capability to have existing Xenon and
new LED strobes in the same field-of-
view
- Fewer power supplies required,
smaller wire gage, reduced wire runs
Straightforward installation
coupled with compact, modern
design
- No visible mounting screws
- Manual (index finger)
slide-setting adjustor
- Four (4) field-selectable
settings in one (1) device:
15cd | 30cd | 75cd | 95cd
Faceplates ship in four
(4) distinctive types:
- ``FIRE’’ | ``ALERT’’ | ``AGENT’’ | (blank)
Two (2) audible settings in
each notification appliance
- Temporal or steady horn output
- High or Low setting
UL (2034 | 1971 | 464) and ULC Listed
(ULC-S525 | - S526); CSFM Approved
- ADA | NFPA | FCC | ANSI | OSHA compliant
Model SLSCW-AL+
Strobe
Model SLHCR-N +
Horn