Specifications

4
Technical Data
SPC4000
20
Siemens AB
A6V10276959
Security Products
18.11.2011
Power supply
Type A (per EN50131-1)
Mains voltage
230 VAC, + 10%/ -15%, 50 Hz
Mains fuse
250 mA T (replaceable part on mains terminal block)
Power consumption
SPC42xx: Max. 160 mA at 230 VAC
SPC43xx: Max. 200 mA at 230 VAC
Operating current
SPC42xx Controller: Max. 160 mA at 12 VDC
SPC43xx Controller: Max. 200 mA at 12 VDC
Quiescent current
SPC42xx Controller:
Max. 140 mA at 12 VDC (165 mA with PSTN, 270 mA
with GSM, 295 mA with PSTN & GSM)
SPC43xx Controller:
Max. 170 mA at 12 VDC (195 mA with PSTN, 300 mA
with GSM, 325 mA with PSTN & GSM)
Output voltage
11-14 VDC in normal conditions (mains powered and
fully charged battery), min. 9.5 VDC when powered by
secondary device (before system shut down to battery
deep discharge protection)
Low voltage trigger
7.5 VDC
Overvoltage protection
15.7 VDC
Peak to Peak ripple
Max. 5 % of output voltage
Auxiliary power (nominal)
Max. 750 mA at 12 VDC
Battery type
SPC422x/4320: YUASA NP7-12FR (7 Ah), Battery not
supplied
Battery charger
SPC422x/4320: Max. 72h to 80% of battery capacity
Battery protection
Current limited to 1 A (fuse protected), deep discharge
protection at 10.5 VDC +/- 3 % (fault at deep discharge
voltage + 0.5 VDC)
Software update
On-site and remote upgrade for controller and
peripherals
Calibration
No calibration checks required (calibrated at
manufacturing)
Servicable parts
No serviceable parts
Operating temperature
0 ~ +40 °C
Relative humidity
Max. 90 % (non condensing)
Colour
RAL 9003 (signal white)
Weight
SPC422x/4320: 4.500 kg
Dimensions (W x H x D)
SPC422x/4320: 264 x 357 x 81 mm
Housing
SPC4320.320: Small metal housing (1.2 mm mild steel)
SPC422x.220: Small housing with metal base (1.2 mm
mild steel) and plastic lid
Housing can contain up to
SPC422x/4320: 1 additional expander (size 150 mm x 82
mm)