SPCK620/623 Comfort Keypad - User Manual
User menus > TEST > WALK TEST
WALK TEST
A walk test ensures that the sensors are operating correctly on the SPC system.
To perform a walk test:
Scroll to TEST > WALK TEST.1.
Press SELECT.2.
The display indicates the number of zones to be tested on the system with the text TO TEST XX (where XX is the
number of valid walk test zones).
Panic zones, Fire zones, Fire Exit zones, and Holdup zones are included in the walk test as activation of these
zone types do not generate an alarm.
NOTICE
Valid walk test zones are defined as all zone types with the exception of Panic zones, Fire zones, Fire Exit zones,
and Holdup zones.
Do not activate zone types during a walk test.
Locate the sensor on the first zone and activate it (open the door or window).1.
The keypad buzzer sounds continuously for approximately 2 seconds to indicate that the zone activation has been
detected and the number of zones left to test (displayed on the keypad) decreases.
Continue with the remaining zones on the system until all zones have been tested. If a zone activation does not get
acknowledged by the system, check the wiring of the sensor and/or replace with another sensor if necessary.
2.