User Manual
7/17
Building Technologies Division CC1N7808en
Infrastructure & Cities Sector 13.05.2016
Technical data
Mains voltage
A
C 220…240 V –15 % +10 %
A
C 100…110 V –15 % +10 %
Mains frequency 50...60 Hz ±6 %
Primary fuse (external) 6.3 AT (customer responsible for
installation)
Type of motor synchronous motor
Power consumption 6.5 VA
A
ngular position max. 160°
Mounting position optional
Degree of protection IP 40 to DIN 40050, provided adequate
cable entries and fixing screws are used
Safety class I to VDE 0631
Cable entry threaded cable gland holder for
1 x Pg9 and 1 x Pg11, no locknut required
cable strain relief to be provided by the use
r
(also refer to «Degree of protection»),
Pg glands for all types are included in the
delivery
Cable connections screw terminals for wires having a cross-
sectional area of 0.5 to 2.5 mm²
Ferrules matching the dia. of the stranded wire
Direction of rotation refer to «Type summary»
Torques and holding torques refer to «Type summary»
Running times refer to «Type summary»
Life cycle Cycles (CLOSED OPEN CLOSED)
at specified torque: typical 250,000
Weight (on average) approx. 800 g
Number of end switches 2
Number of auxiliary switches refer to «Type summary»
A
ctuation via camshaft, color-coded cams (refer to
«Connection diagrams»
Switching voltage
A
C 24...250 V
A
djustment of cams in increments of 1°
Perm. terminal rating at cos = 0,9:
Electronic circuit
Peak current Operating current
- under load ON, not under load OFF
- under load ON, under load OFF
Max. 14 A
Max. 7 A
2 A
1 A
Storage
DIN EN 60 721-3-1
Climatic conditions
class 1K2
Mechanical conditions
class 1M2
Temperature range
-20...+60 °C
Humidity
< 95 % r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions
class 2K2
Mechanical conditions
class 2M2
Temperature range
-20...+60 °C
Humidity
< 95 % r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions
class 3K3
Mechanical conditions
class 3M3
Temperature range
-20...+60 °C
Humidity
< 95 % r.h.
Attention!
Condensation, formation of ice and ingress of water are not permitted!
General actuator data
Actuator
End and auxiliary
switches
Environmental
conditions