Electromotoric actuator SSA151.05HF, SSA161.05HF, SSA161E.05HF For pressure independent combi valves (PICV), radiator valves, MiniCombi valves (MCV) and small globe valves ● ● ● ● ● ● ● ● A6V11858278_en--_c 2021-08-06 SSA151.05HF: Operating voltage AC/DC 24 V, positioning signal DC 4...20 mA SSA161.05HF, SSA161E.05HF: Operating voltage AC/DC 24 V, positioning signal DC 0...
Use ● ● ● ● ● ● ● For radiator valves, VDN.., VEN.., VUN.. For Siemens PICV (pressure independent combi valves) VPP46.. and VPI46.. For MiniCombi valves VPD.., VPE.. For small valves VD1..CLC For radiator valves (M30 × 1.5) from other manufacturers without adapter Typically in radiator, chilled ceiling, VAV and fan coil unit applications Max.10 units of SSA161.05HF/SSA161E.05HF are able to operate in parallel, provided the controller output suffices. NOTICE SSA161E.05HF is only compatible with VPD.., VPE.
DC 0...10 V control signal (for SSA161.05HF) ● ● ● ● The valve opens / closes in proportion to the control signal at Y. At DC 0 V, actuator stem extended, the valve is fully closed. When no power is supplied, the actuator maintains its current position. This actuator provides a DC 0…10 V position feedback signal proportional to the stroke of the actuator stem. Y = Control signal Y [V] H = Percentage of calibrated valve stroke DC 0...10 V control signal (for SSA161E.05HF) Combi valves VPI46../VPP46..
Type summary Type Stock number Operating voltage Running speed Running time 2.5 mm Control signal Actuator characteristic Cable length SSA151.05HF S55180-A110 AC/DC 24 V 10 s/mm 25 s DC 4…20 mA Linear 1.5 m SSA161.05HF S55180-A108 AC/DC 24 V 10 s/mm 25 s DC 0...10 V Linear 1.5 m SSA161E.05HF S55180-A109 AC/DC 24 V 10 s/mm 25 s DC 0...10 V Equal percentage 1.5 m Ordering When ordering, specify both type and quantity. Example: Type Stock number Designation Quantity SSA161.
Combinable valves for SSA161E.05HF Type reference Valve type Kvs VPP46.., VPI46.. PICV valves DN10..DN32 3 V̇ PN class Data sheet [m /h] [I/h] - 30…4001 PN 25 N4855 Kvs: Nominal flow rate of cold water (5…30 °C) through the fully open valve (H100) by a differential pressure of 100 kPa (1 bar). Note: To ensure trouble-free operation of third-party valves with the SSA.. actuator, the valves must satisfy the following requirements: ● Threaded connections with coupling nut M30 × 1.5.
Product documentation Topic Title Document ID: 1) Mounting and installation Mounting instructions Standards and directives CE declarations A5W00106106A RCM conformity A5W00106107A Environmental declarations A5W00109220A Environmental compatibility 1) A6V11858272 The mounting instructions is enclosed in product packaging. Related documents such as environmental declarations, CE declarations etc., can be downloaded from http://siemens.com/bt/download.
Orientation Installation A [mm] B [mm] C [mm] 5.5 4.2 50 Crimp ferrule on stripped wire of connecting cable. ● Observe all admissible temperatures (see “Technical data [▶ 11]”). ● ● ● Do not twist the cable. Magnets can damage the actuator. Provide a means for isolation from the power supply, e.g., connecting a circuit breaker or switch fuse upstream of the control unit.
NOTICE The actuator must be commissioned only with a correctly mounted valve in place! Self-calibration When operating voltage is applied, the actuator self-calibrates (fully retracted ➙ fully extended ➙ setpoint). CAUTION Never intervene manually during self-calibration. NOTICE ● Correct calibration is only possible with valve stroke > 1.2 mm. Valve stroke < 1.2 mm results calibration failure. ● If calibration fails, the actuator performs another calibration automatically after 10 seconds.
WARNING If operating voltage is switched on, press button (a) before and after adjusting the position of the actuator stem. If you switched off operating voltage and control signal, you can adjust the position directly without pressing button (a). Maintenance The actuators require no maintenance. WARNING Operating voltage must be switched off during any maintenance! NOTICE When carrying out service work on the plant, note the following: ● Switch off operating voltage.
Open Source Software (OSS) Software license overview These devices use Open Source Software (OSS). All Open Source Software components used in the product (to include copyrights and licensing agreement) are available at http://siemens.com/bt/download. Firmware version OSS document Device Document ID Title 1.8.0 A6V12067557 Readme OSS "MRA Modulating – 1.1" SSA161.05HF SSA151.05HF SSA161E.
Technical data Power supply Operating voltage AC 24 V (± 15 %) or DC 24 V (± 20 %) Frequency 50/60 Hz Power consumption Running 2.5 VA Holding 2 VA Primary fuse or breaker rating External, 2 A quick blow Signal input SSA151.05HF SSA161.05HF/SSA161E.05HF Control signal 4…20 mA DC 0...10 V Input impedance 150 Ohm 100 kOhm Parallel operation (number of actuators) 1 Max. 101) Signal output SSA151.05HF SSA161.05HF/SSA161E.05HF Feedback signal 4…20 mA DC 0...10 V Max.
Standards EU conformity (CE) A5W00106106A RCM conformity A5W00106107A Housing protection degree IP 54 Protection class according to EN 60730 III Environmental compatibility The product environmental declaration (A5W00109220A) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Diagrams Connection terminals Code No. Color Abbreviation Meaning SSA151.05HF SSA161.05HF/ SSA161E.05HF G 1 Red RD System potential AC 24 V (+ DC 24 V) System potential AC 24 V (+ DC 24 V) Y 8 Grey GY Control signal DC 4...20 mA, < 3 V Control signal DC 0...10 V, < 0.
Dimensions Revision numbers Type Valid from rev. no. SSA151.05HF ..A SSA161.05HF ..A SSA161E.05HF ..
Issued by Beijing Siemens Cerberus Electronics Ltd. Smart Infrastructure No.1, Fengzhi East Road, Xibeiwang Haidian District, 100094 BEIJING, China +86 10 64768806 www.siemens.com/buildingtechnologies Document ID A6V11858278_en--_c Edition 2021-08-06 © Beijing Siemens Cerberus Electronics Ltd., 2021 Technical specifications and availability subject to change without notice.