Electromotoric actuator SSA151.05HF, SSA161.05HF, SSA161E.05HF For pressure independent combi valves (PICV), radiator valves, MiniCombi valves (MCV) and small globe valves ● ● ● ● ● ● ● ● A6V11858278_en--_a 2020-07-30 SSA151.05HF: Operating voltage AC/DC 24 V, positioning signal DC 4...20 mA SSA161.05HF, SSA161E.05HF: Operating voltage AC/DC 24 V, positioning signal DC 0...
Use ● ● ● ● ● ● ● For radiator valves, VDN.., VEN.., VUN.. For Siemens PICV (pressure independent combi valves) VPP46.. and VPI46.. For MiniCombi valves VPD.., VPE.. For small valves VD1..CLC For radiator valves (M30 × 1.5) from other manufacturers without adapter Typically in radiator, chilled ceiling, VAV and fan coil unit applications Max.10 units of SSA161.05HF/SSA161E.05HF are able to operate in parallel, provided the controller output suffices. NOTICE SSA161E.05HF is only compatible with VPP46..
DC 0...10 V control signal (for SSA161E.05HF) Combi valves VPI46../VPP46.. in combination with SSA161E.05HF have equal-percentage characteristics. ● ● ● ● The valve opens / closes in equal percentage ratio to the control signal at Y. At DC 0 V, actuator stem extended, the valve is fully closed. When no power is supplied, the actuator maintains its current position. This actuator provides a DC 0…10V position feedback signal proportional to the stroke of the actuator stem.
Equipment combinations Valves Combinable valves for SSA151.05HF and SSA161.05HF Type reference Valve type Kvs [m3/h] V̇ [I/h] PN class Data sheet VDN.., VEN.., VUN.. Radiator valves 0.09…1.41 - PN 10 VPD.., VPE.. MCV radiator valves - 25…483* N2185 VD1..CLC Small valves 0.25…2.60 - N2103 VPP46.., VPI46.. PICV valves DN10..
Combinable room thermostats for SSA161.05HF and SSA161E.05HF Type Detail RDG.. RDG160KN, RDG160T, RDG405KN RDU.. RDU340 RCU.. RCU50.. NOTICE SSA151.05HF cannot be used in combination with the above thermostats as its control signal of DC 4...20 mA is not supported by these thermostats.
● ● Position the actuator and tighten the union nut manually. See Mounting instructions enclosed with the product package for graphical instructions. Orientation Installation A [mm] B [mm] C [mm] 5.5 4.2 50 Crimp ferrule on stripped wire of connecting cable. ● ● ● ● Observe all admissible temperatures (see “Technical data [➙ 10]”). Do not twist the cable. Magnets can damage the actuator. Provide a means for isolation from the power supply, e.g.
NOTICE The actuator must be commissioned only with a correctly mounted valve in place! Self-calibration When operating voltage is applied, the actuator self-calibrates (fully retracted ➙ fully extended ➙ setpoint). CAUTION Never intervene manually during self-calibration. NOTICE ● ● ● Correct calibration is only possible with valve stroke > 1.2 mm. Valve stroke < 1.2 mm results calibration failure. If calibration fails, the actuator performs another calibration automatically after 10 seconds.
WARNING If operating voltage is switched on, press button (a) before and after adjusting the position of the actuator stem. If you switched off operating voltage and control signal, you can adjust the position directly without pressing button (a). Maintenance The actuators require no maintenance. WARNING Operating voltage must be switched off during any maintenance! NOTICE When carrying out service work on the plant, note the following: ● ● ● Switch off operating voltage.
Open Source Software (OSS) Software license overview These devices use Open Source Software (OSS). All Open Source Software components used in the product (to include copyrights and licensing agreement) are available at http://siemens.com/bt/download. Firmware version OSS document Document ID 1.8.0 Siemens Smart Infrastructure Device Title A6V12067557 Readme OSS "MRA Modulating – 1.1" SSA161.05H F SSA151.05H F SSA161E.
Technical data Power supply Operating voltage AC 24 V (± 15 %) or DC 24 V (± 20 %) Frequency 50/60 Hz Power consumption Running 2.5 VA Holding 2 VA Primary fuse or breaker rating External, 2 A quick blow Signal input SSA151.05HF SSA161.05HF/SSA161E.05HF Control signal 4…20 mA DC 0...10 V Input impedance 150 Ohm 100 kOhm Parallel operation (number of actuators) 1 Max. 101) 1) Provided that the controller output is sufficient. Signal output SSA151.05HF SSA161.05HF/SSA161E.
Housing color Cover/base RAL 9003, signal white Coupling nut RAL 7035, light gray General ambient conditions Operation EN 60721-3-3 Transport EN 60721-3-2 Storage EN 60721-3-1 Environmental conditions Class 3K3 Class 2K3 Class 1K3 Temperature 1...50 ℃ -25...70 ℃ -5...50 ℃ Humidity 5...85 % r.h. <95 % r.h. 5...95 % r.h.
Diagrams Connection terminals Code No. Color Abbreviation Meaning SSA151.05HF SSA161.05HF/ SSA161E.05HF G 1 Red RD System potential AC 24 V (+ DC 24 V) System potential AC 24 V (+ DC 24 V) Y 8 Grey GY Control signal DC 4...20 mA, < 3 V Control signal DC 0...10 V, < 0.
Dimensions Revision numbers Siemens Smart Infrastructure Type Valid from rev. no. SSA151.05HF ..A SSA161.05HF ..A SSA161E.05HF ..
Issued by Beijing Siemens Cerberus Electronics Ltd. Smart Infrastructure No.1, Fengzhi East Road, Xibeiwang Haidian District, 100094 BEIJING, China Tel. +86 10 64768806 www.siemens.com/buildingtechnologies 14 Siemens Smart Infrastructure Document ID A6V11858278_en--_a Edition 2020-07-30 © Beijing Siemens Cerberus Electronics Ltd., 2020 Technical specifications and availability subject to change without notice.