Data Sheet for Product

599 Series Zone Valve and Actuator Assembly Selection Technical Bulletin TB254
Document Number 155-291
February 9, 2018
Siemens Industry, Inc. Page 3
Figure 1. Water Capacity Graph.
Table 1. Maximum Water Capacity - U.S. Gallons per Minute (ABA).
Valve
Size
Inches
Cv\1
2
3
4
5
6
8
10
15
20
25
30
40
50
60
75
.50
1.0
1.4
1.7
2.0
2.2
2.4
2.8
3.2
3.9
4.4
5.0
5.5
6.3
7.1
7.7
8.7
.50
2.5
3.5
4.3
5.0
5.6
6.1
7.1
7.9
9.7
11.2
12.5
13.7
15.8
17.7
19.4
22.0
.50/.75
4.1
5.7
7.1
8.2
9.2
10.0
11.6
13.0
15.9
18.3
20.5
22.4
25.9
29.0
31.8
35.5
1.00
7.0
9.9
12.1
14.0
15.6
17.1
19.8
22.1
27.1
31.3
35.0
38.3
44.3
49.5
54.2
60.6
Table 2. Maximum Water Capacity - Cubic Meters per Hour (m
3
/hr) (ABA).
Valve
Size
Mm
Pressure Differential - kPa
1
10
20
30
40
50
60
80
Kvs/100
150
200
300
400
500
15
0.9
0.27
0.38
0.47
0.54
0.60
0.66
0.76
0.85
1.04
4.20
1.47
1.70
1.90
15
0.21
0.68
0.96
1.17
1.35
1.51
1.66
1.91
2.15
2.60
3.00
3.70
4.30
4.80
15/20
0.35
1.12
1.59
1.94
2.24
2.51
2.75
3.17
3.50
4.34
5.01
6.14
7.09
7.93
25
0.60
1.91
2.71
3.32
3.83
4.28
4.69
5.41
6.00
7.41
8.56
10.48
12.11
13.54