Data Sheet for Product

‘ST’ (for MNS) Series Notification Appliances
2588
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
Notification Appliances
ST
Mass Notification Clear & Amber Lens Standalone Strobe Appliances
Application: Indoor
Product Overview
The Model ST-series of strobes, used in correlation to mass-notification appliances, are a cost-
effective way to retrofit colored-lens strobe appliances. Each Model ST-series strobe easily mounts
to standard 4” backboxes, or for surface-mount use with Siemens Model SBL2S surface backbox.
UL Listed for use with UL2572 Listed mass-notification systems
Strobes are available in A
MBER and CLEAR lens
Devices specific to mass notification will have the word ‘A
LERT’ appear
on its cover in red-or-white text
Strobes operate from 16 to 33VDC [using filtered or Full-Wave Rectified (FWR) voltage]
Intensity options for AMBER-lens strobes include multi-Candela models with four (4)
field-selectable Candela settings or 110 Candela models
Strobes can be synchronized using the Siemens DSC sync modules, and are utilized
as mass-notification devices, per
UL 2572:
The 252 / 504-point addressable intelligent voice communication system from Siemens
FireFinder® XLSM panels
PAD-series NAC Extenders with built-in sync protocol
Available with a CLEAR lens or AMBER-lens option for mass notification:
Ceiling models are available with field-selectable, CLEAR-lens Candela settings of 15 / 30 / 75 / 95cd
Wall-mount models are available with field-selectable, CLEAR-lens Candela settings of 15 / 30 / 75 / 110cd
Ceiling models are available with field-selectable, AMBER-lens Candela settings of 11 / 22 / 56 / 71cd
Wall-mount models are available with field-selectable, AMBER-lens Candela settings of 11 / 22 / 56 / 82cd
UL Standard 1971 Listed;
Complies with Occupational Safety and Health Administration (OSHA) 29, Part 1910.165
Clear-Lens Strobe Ceiling Mount
(ST-CMC-CW-MNS-ALERT)
Amber-Lens Retrofit Strobe Wall Mount
(ST-AMC-RETRO-W-MNS-ALERT)
Amber-Lens Strobe Wall Mount
(ST-AMC-R-MNS-ALERT)