Error code
(W#16#...):
Description
0000 No error
0081 The target range is larger than the source range.
The source area is written completely to the target area. The remaining bytes of
the target area are filled with 0.
7000 First call with REQ=0: no data transfer active; BUSY has the value 0.
7001 First call with REQ=1: no data transfer active; BUSY has the value 1.
7002 Intermediate call (REQ irrelevant): data transfer already active; BUSY has the
value 1.
8081 The source range is larger than the target range.
The target range is fully written. The remaining bytes of the source area are
ignored.
8091 You have called the SFC 82 nested.
8092 The operation "Generate a DB" is currently not executable because
The "Compress Application Memory" operation is currently active
The maximum number of blocks on your CPU has already been reached.
8093 No data block or a data block that is not in the work memory is indicated for the
parameter SRCBLK.
8094 A not yet supported attribute was specified for the ATTRIB parameter
80A1 DB number error:
the number is 0
Lower limit > Upper Limit
80A2 DB length error:
the length is 0
the length is an odd number
the length is higher than permitted by the CPU
80B1 No free DB number
80B2 Insufficient memory
80BB Insufficient load memory
80C0 The target is currently being processed by another SFC or communication
operation.
80C3 The maximum number of simultaneously active SFC 82 is currently reached.
8xyy General error codes, for example:
Source DB does not exist or it is only available as copied version
Source area in DB does not exist