Technical data

Table Of Contents
SFCs/SFBs for Transferring Data Records
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
7-17
Error Code
(W#16#...)
Explanation
Restriction
80B1 The length specified in the RECORD parameter is
incorrect.
SFC 58 "WR_REC":
Length incorrect
SFC 59 "RD_REC"
(only when using old
S7-300 FMs and S7-
300
CPs): specified length >
record length
With SFC 13
"DPNRM_DG":
specified length >
record length
80B2 The configured slot is not occupied. -
80B3 Actual module type does not match the required module
type in SDB1
-
80C0 For SFC 59 (RD_REC): The module has the data record,
but there are still no data to be read.
For SFC 13 (DPNRM_DG): There are no diagnostic data
available.
Only for SFC 59 "RD_REC"
or SFC 13 "DPNRM_DG"
80C1 The data of the previous write job for the same data record
on the module have not yet been processed by the module.
-
80C2 The module is currently processing the maximum possible
number of jobs for a CPU.
-
80C3 The required resources (memory, etc.) are currently
occupied.
-
80C4 Internal temporary error. The job could not be processed.
Repeat the job. If this error occurs frequently check
your system for electrical disturbance sources.
-
80C5 Distributed I/Os not available. Distributed I/Os
80C6 Data record transfer was stopped due to a priority class
abort (restart or background)
Distributed I/Os
8xyy General error codes, see Evaluating Errors with Output
Parameter RET_VAL
7.9 Further Error Information for SFCs 55 to 59
S7-400 only
With the S7-400, the SFCs 55 to 59 can also return the error information
W#16#80Fx. In this case an error occurred that could not be localized. Please