Target Area TINFO and AINFO
Dependent on the respective OB in which SFB54 is called, the target areas TINFO
and AINFO are only partially written. Refer to the table below for information on
which info is entered respectively.
Interrupt type OB TINFO
OB status
information
TINFO
management
information
AINFO
header
information
AINFO
additional interrupt
information
central: No Hardware
interrupt
4x Yes Yes Yes
distributed: as delivered by the
PROFIBUS DP
slave/PROFINET IO
device
Status interrupt 55 Yes Yes Yes Yes Yes
Update Interrupt 56 Yes Yes Yes Yes Yes
manufacturer
specific
interrupt
57 Yes Yes Yes Yes Yes
Peripheral
redundancy error
70 Yes Yes No No No
central: Data record 1 Diagnostic
interrupt
82 Yes Yes Yes
distributed: As delivered by the
PROFIBUS DP
slave/PROFINET IO
device
central: No Removal/
Insertion
interrupt
83 Yes Yes Yes
distributed: as supplied by
PROFIBUS DP
slave/PROFINET IO
device
Special form of
the removal
interrupt:
Controlled by
supervisor
83 Yes Yes Yes Only PROFINET IO
Special form of
the insertion
interrupt:
Controlled by
supervisor
83 Yes Yes Yes Only PROFINET IO
Unconfigured
module inserted
83 Yes Yes Yes Only PROFINET IO
Module rack/
Station failure
86 Yes Yes No No
...
all other OBs
Yes No No No