Technical data

Table Of Contents
DPV1 SFBs According to PNO AK 1131
System Software for S7-300/400 System and Standard Functions - Volume 1/2
8-18
A5E00709327-01
STATUS[3] can have the following values:
Error_Decode
(B#16#...)
Error_Code_1
(B#16#...)
Explanation
according to
DVP1
Meaning
00 00 no error, no warning
00 reserved, reject initial call; no active data record transfer
01 reserved, reject initial call; data record transfer has started
70
02 reserved, reject intermediate call; data record transfer already active
90 reserved, pass invalid logical start address
92 reserved, pass illegal type for ANY pointer
93 reserved, pass The DP component addressed via ID or F_ID is not
configured.
95 Error in the H system when fetching additional
interrupt information (when fetching additional
interrupt information at the local or distributed I/O via
an external DP interface, this error is output as "group
error".)
Note: When connecting or updating the additional
interrupt information may not be available temporarily.
96 A master-reserve switchover has occurred in an H
system, and the previous master CPU has gone into
STOP mode. At that time, an OB was being
processed. SFB 54 cannot supply the OB start
information, management information, header
information or additional interrupt information.
You can read out the OB start information with SFC 6
"RD_SINFO". In addition, you can use SFC 13
"DPNRM_DG" to synchronously read the current
diagnostic frame of the affected DP slave for OBs 4x,
55, 56, 57, 82 and 83 (Address information from the
OB start information).
A0 read error Negative acknowledgement while reading the module.
A1 write error negative acknowledgement while writing the module
A2 module failure DP protocol error at layer 2
A3 reserved, pass
PROFIBUS DP: DP protocol error with Direct-
Data-Link-Mapper or User-Interface/User
PROFINET IO: General CM error
A4 reserved, pass Bus communication disrupted
A5 reserved, pass
A7 reserved, pass DP slave or modules is occupied (temporary error
A8 version conflict DP slave or modules reports non-compatible versions
80
A9 feature not
supported
Feature not supported by DP slave or module