Technical data

Table Of Contents
DPV1 SFBs According to PNO AK 1131
System Software for S7-300/400 System and Standard Functions - Volume 1/2
8-20
A5E00709327-01
Error_Decode
(B#16#...)
Error_Code_1
(B#16#...)
Explanation
according to
DVP1
Meaning
00 to FF Error in the initial call parameter (with SFB54: MODE)
81
00 Illegal operating mode
82 00 to FF Error in the second call parameter
: : :
00 to FF Error in the eighth call parameter (with SFB54:
TINFO)
01 Wrong syntax ID
23 Quantity frame exceeded or target area too small
24 Wrong range ID
32 DB/DI no. out of user range
88
3A DB/DI no. is NULL for area ID DB/DI or specified
DB/DI does not exist
00 to FF Error in the ninth call parameter (with SFB54: AINFO)
01 Wrong syntax ID
23 Quantity frame exceeded or target area too small
24 Wrong range ID
32 DB/DI no. out of user range
89
3A DB/DI no. is NULL for area ID DB/DI or specified
DB/DI does not exist
8A 00 to FF Error in the 10th call parameter
: : :
8F 00 to FF Error in the 15th call parameter
FE, FF 00 to FF Profile-specific error
With DPV1 errors, the DP Master passes on STATUS[4] to the CPU and to the
SFB. Without DPV1 error, this value is set to 0, with the following exceptions for the
SFB 52:
STATUS[4] contains the target area length from RECORD, if MLEN > the target
area length from RECORD
STATUS[4]=MLEN, if the actual data record length < MLEN < the target area
length from RECORD
STATUS[4]=0, if STATUS[4] > 255 would have to be set