SFCs for Diagnostics
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
13-9
SSL_ID (W#16#...) Partial List INDEX (W#16#...)
0692 Diagnostic status of the expansion racks in a central
configuration /
of the stations of a DP master system connected via an
integrated DP interface module
0 / DP master system
ID
4692 Diagnostic status of the stations of a DP master system
connected
via an external DP interface module
DP master system ID
Extended DP master system information
0195 Extended information about a DP master system
DP master system ID
0F95 Only info in SSL partial list headers 0000
Diagnostic buffer
(a maximum of 21 data records is
supplied)
00A0 All entries that can be supplied in the currently active
operating mode
Irrelevant
01A0 The most recent entries, the number is specified in the
index
Quantity
0FA0 Only SSL partial list header information Irrelevant
Diagnostic data on modules
00B1 The first four diagnostic bytes of one module (data record 0) Logical base address
00B2 All diagnostic data of one module (
<
220 bytes, data record 1)
(no DP module)
Rack, slot
00B3 All diagnostic data of one module (
<
220 bytes, data record 1) Logical base address
00B4 Diagnostic data of a DP slave Configured
diagnostic
address