Technical data

Table Of Contents
SFCs for Diagnostics
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
13-25
Error information
When looking at the "real" error information (error codes W#16#8xyz) in the
following table, we distinguish between two types of event:
Temporary errors (error codes W#16#80A2 to 80A4, 80C3, 80C5):
This type of error is possibly eliminated without user action, meaning it is
helpful to call the SFC again (multiple calls, if necessary).
Example of a temporary error: Resources required are currently in use
(W#16#80C3).
Permanent errors (error codes W#16#8082, 80B0, 80B2):
This type of error does not correct itself. A new call of the SFC only makes
sense after you have eliminated the error. Example of a permanent error: The
DP master / CPU does not support this service. (W#16#80B0).
Error code
(W#16#...)
Explanation
0000 The job was completed without error.
7000 Initial call with REQ=0. Bus topology identification is not initiated. BUSY = 0.
7001 Initial call with REQ=1. Bus topology identification was requested. BUSY = 1.
7002 Intermediate call (REQ irrelevant): Topology identification is still busy. BUSY = 1.
7010 You have requested to cancel the topology identification. However, there is no busy job
which matches the specified DP_ID. BUSY = 0.
7011 Initial call with R=1. The request to cancel topology identification was initiated.
BUSY = 1.
7012 Intermediate call: Topology identification has not yet been completed. BUSY = 1.
7013 Final call: Topology identification was cancelled. BUSY = 0.
8082 No DP master system configured with the specified DP_ID.
80A2 Error during topology identification; for more detailed information please refer to output
parameters DPR and DPRI.
80A3 Error during topology identification: Watchdog timeout.
80A4 Communication error at the am K bus
80B0 The DP master / CPU does not support this service.
80B2 Error during topology identification: No diagnostics repeater was found at the selected
DP master system.
80C3 Resources required are currently in use. Possible causes: You have initiated a second
topology identification cycle (only one topology identification cycle is permitted at a given
time) or the H CPU is performing a connecting or update action.
80C5 The DP master system is currently not available.
8xyy General error information, see Evaluating Errors with Output Parameter RET_VAL