Technical data

Table Of Contents
SFCs and SFBs for Updating the Process Image and Processing Bit Fields
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
14-5
Error information
Event class
Error code
Explanation
W#16#8090 Illegal value at parameter PART or and update of the specified process image partition
input table is not a not permitted in this OB. The process image partition input table was
not updated.
W#16#8091 The specified process image partition was still not defined or is not located in a
accessible process image area on the CPU. The process image partition input table
was not updated.
W#16#80A0 During updating an access error was detected. The affected inputs were set to "0".
W#16#80A1 The update time lies after the permitted access window . The process image partition
input table was not updated.
The DP cycle is too short to ensure enough time for SFC processing. You will have to
increase the TDP, Ti and To times in STEP 7.
W#16#80C1 The update time lies before the permitted access window. The process image partition
input table was not updated.
W#16#8xyy General error information, see Evaluating Errors with Output Parameter RET_VAL
Note
When using SFC 126 "SYNC_PI" for the process image partitions of DP standard
slaves for which you have defined a consistency range greater than 32 bytes, the
error codes of SFC 14 "DPRD_DAT" are also available.