Technical data

Table Of Contents
SFCs and SFBs for Updating the Process Image and Processing Bit Fields
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
14-7
Error information
Event class
Error code
Explanation
W#16#0001 Consistency warning. The update of the process image partition table was distributed
over two DP cycles. However, the data in one slave were consistently transferred.
W#16#8090 Illegal value at parameter PART or and update of the specified process image partition
output table is not a not permitted in this OB. Outputs were not transferred to the I/O
devices. The process image partition output table was not changed.
W#16#8091 The specified process image partition was still not defined or is not located in a
accessible process image area on the CPU. Outputs were not transferred to the I/O
devices. The process image partition output table was not changed.
W#16#80A0 During updating an access error was detected. Outputs were not transferred to the I/O
devices. The process image partition output table was not changed.
W#16#80A1 The update time lies after the permitted access window or the output data were not
updated by the DP master. Outputs were not transferred to the I/O devices. The process
image partition output table was not changed.
The DP cycle is too short to ensure enough time for SFC processing. You will have to
increase the TDP, Ti and To times in STEP 7.
W#16#80C1 The update time lies before the permitted access window. Outputs were not transferred
to the I/O devices. The process image partition output table remains unchanged.
W#16#8xyy General error information, see Evaluating Errors with Output Parameter RET_VAL
Note
When using SFC 127 "SYNC_PO" for the process image partitions of DP
standard slaves for which you have defined a consistency range greater than
32 bytes, the error codes of SFC 15 "DPWR_DAT" are also available.