Technical data

Table Of Contents
System Functions for Addressing Modules
System Software for S7-300/400 System and Standard Functions - Volume 1/2
15-2
A5E00709327-01
Error Information
Error Code (W#16#...) Explanation
0000 No error occurred.
8094 No subnet was configured with the specified SUBNETID.
8095 Illegal value for the RACK parameter.
8096 Illegal value for the SLOT parameter.
8097 Illegal value for the SUBSLOT parameter.
8098 Illegal value for the SUBADDR parameter.
8099 The slot is not configured or occupied by a submodule with packed
addresses (ET 200S).
809A The sub address of the selected slot is not configured (only
possible with central IO devices for CPU and IM).
8xyy General error information, see Evaluating Errors with Output
Parameter RET_VAL