Technical data

Table Of Contents
System Functions for Addressing Modules
System Software for S7-300/400 System and Standard Functions - Volume 1/2
15-4
A5E00709327-01
Output Parameter AREA
The output parameter AREA specifies how the output parameters RACK, SLOT
and SUBADDR must be interpreted (see following table).
Value of AREA System Meaning of RACK, SLOT and SUBADDR
0 S7-400 RACK : Module rack no.
SLOT : Slot no.
SUBADDR : Difference between logical address and logical
base address
1 S7-300 RACK: Module rack no.
SLOT : Slot no.
SUBADDR : Difference between logical address and logical
base address
2 DP RACK: (low byte) Station number
RACK : (high byte) DP Master system ID
SLOT : Slot no. in the station
SUBADDR : Offset in the user data address area of the
corresponding module.
3 S5 P area RACK: Module rack no.
SLOT : Slot no. of the adaptation capsule
SUBADDR : Address in the S5 x range
4 S5 O area RACK: Module rack no.
SLOT : Slot no. of the adaptation capsule
SUBADDR : Address in the S5 x range
5 S5 IM3 area RACK: Module rack no.
SLOT : Slot no. of the adaptation capsule
SUBADDR : Address in the S5 x range
6 S5 IM4 area RACK: Module rack no.
SLOT : Slot no. of the adaptation capsule
SUBADDR : Address in the S5 x range
Error Information
Error Code (W#16#...) Explanation
0000 No error occurred.
8090 Specified logical address invalid or illegal value for the IOID parameter
8093 This SFC is invalid for the module selected by means of IOID and LADDR.
8xyy General error information, see Evaluating Errors with Output Parameter
RET_VAL