Technical data

Table Of Contents
SFCs for Distributed I/Os or PROFINET IO
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
16-3
Error Information
Error Code (W#16#...) Explanation
0000 The job was executed without errors.
7000 First call with REQ=0. No hardware interrupt request is active; BUSY has
the value 0.
7001 First call with REQ=1. A hardware interrupt request has already been sent to
the DP master; BUSY has the value 1.
7002 Interim call (REQ irrelevant): the triggered hardware interrupt has not yet
been acknowledged by the DP master; BUSY has the value 1.
8090 Start address of the address range in the transfer memory is incorrect.
8091 Interrupt is blocked (block configured by user)
8093 The parameters IOID and LADDR address a module that is not capable of a
hardware interrupt request.
80B5 Call in the DP master not permitted.
80C3 The required resources (memory, etc.) are occupied at this time.
80C5 Distributed I/O device is not available at this time (i.e. station failure).
80C8 The function is not permitted in the current DP master operating mode.
8xyy General error information, see Evaluating Errors with Output Parameter
RET_VAL