Technical data

Table Of Contents
SFCs for Distributed I/Os or PROFINET IO
System Software for S7-300/400 System and Standard Functions - Volume 1/2
16-14
A5E00709327-01
Error code (W#16#...) Explanation
80A1 The addressed component could not be assigned parameters (this error code is
possible only with MODE = 1.)
Note:
The CPU supplies this information only if the activated slave fails again during
parameter assignment. If parameter assignment of a single module was
unsuccessful, the SFC returns the error information W#16#0000.
80A2 The addressed DP slave does not return an acknowledgement.
80A3 The DP Master/PROFINET IO controller concerned does not support this
function.
80A4 The CPU does not support this function for external DP masters/PROFINET IO
controller.
80A6
Slot error in the DP slave/PROFINET IO device; not all user data can be
accessed (this error code is only available for MODE=1).
Note:
The SFC returns this error information only if the active component fails after
parameter assignment and before the SFC ends. If only a single module is
unavailable the SFC returns the error information W#16#0000.
80C1
SFC12 was started and continued with another logical address (this
error code is only available for MODE=1).
80C3
Temporary resource error: The CPU is currently processing the maximum
possible activation and deactivation jobs. (this error code is possible only
with MODE = 1 and MODE = 2.)
The CPU is busy receiving a modified configuration. Currently you can not
enable/disable DP slaves/PROFINET IO devices.
8xyy
error information, see Evaluating Errors with Output Parameter RET_VAL