ERROR
STATUS
(Decimal)
Explanation
1 20
S7-400: Not enough work memory available. If there is still enough total
work memory available, then the solution is to compress the work
memory.
H system: a first call of SFB is not possible during an update since the
communication buffer in the work memory is being created. Measures
that change the work memory are not possible during an update.
S7-300:
-
Maximum number of parallel jobs/instances exceeded
-
The instances were overloaded at CPU-RUN (STOP-RUN transition
of the CPU or CP required.)
-
Possible when first called
-
Memory bottleneck in CP
1 27 There is no function code in the CPU for this block.
Data Consistency
To ensure data consistency, you can only write to the currently used send area
SD_i again after the current send operation is complete. This is the case when the
value of the status parameter DONE changes to 1.