Technical data

Table Of Contents
S7 Communication
System Software for S7-300/400 System and Standard Functions - Volume 2/2
21-28
A5E00739858-01
ERROR
STATUS
(Decimal)
Explanation
1 20
S7-400: Not enough work memory available. If there is still enough total
work memory available, then the solution is to compress the work memory.
H system: a first call of SFB is not possible during an update since the
communication buffer in the work memory is being created. Measures that
change the work memory are not possible during an update.
S7-300:
-
Maximum number of parallel jobs/instances exceeded
-
The instances were overloaded at CPU-RUN (STOP-RUN transition of
the CPU or CP required.)
-
Possible when first called
1 27 There is no function code in the CPU for this block.
Data Consistency
The data are received in a consistent state if the following point is observed:
Evaluate the part of the receive area RD_i currently being used completely before
initiating another job.