Technical data

Table Of Contents
Organization Blocks
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
1-27
The following table shows which event caused OB72 to be started.
OB72_EV_CLASS OB72_FLT_ID Start Event of OB72
B#16#73 B#16#01 Loss of redundancy (1 of 2) due to a CPU failure
B#16#73 B#16#02 Loss of redundancy (1 of 2) due to STOP on the reserve triggered
by user
B#16#73 B#16#03 H system (1 of 2) changed to redundant mode
B#16#73 B#16#20 Error in RAM comparison
B#16#73 B#16#21 Error comparing process image output value
B#16#73 B#16#22 Error comparing memory bits, timers, or counters
B#16#73 B#16#23 Different operating system data recognized
B#16#73 B#16#31 Standby-master switchover due to master failure
B#16#73 B#16#33 Standby-master switchover due to system modification during
runtime
B#16#73 B#16#34 Standby-master switchover due to sync module connection
problem
B#16#73 B#16#40 Synchronization error in user program due to elapsed wait time
B#16#73 B#16#41 Synchronization error in user program due to waiting at different
synchronization
points
B#16#73 B#16#42 Synchronization error in operating system due to waiting at
different
synchronization points
B#16#73 B#16#43 Synchronization error in operating system due to elapsed wait
time
B#16#73 B#16#44 Synchronization error in operating system due to wrong data
B#16#79 B#16#50 No SYNC module
B#16#79 B#16#51 Modification at SYNC module without Power On
B#16#79/B#16#78 B#16#52 SYNC module removed/inserted
B#16#79 B#16#53 Modification at SYNC module without reset
B#16#79 B#16#54 SYNC module: rack number assigned twice
B#16#79/B#16#78 B#16#55 SYNC module error/eliminated
B#16#79 B#16#56 Illegal rack number set on the SYNC module
B#16#73 B#16#C1 Updating aborted
B#16#73 B#16#C2 Abort of update attempt because a monitoring time was exceeded
during the n-th attempt (1 <= n <= maximum possible number of
update attempts after an abort due to the monitoring time being
exceeded.)