Technical data

Table Of Contents
Open Communication via Industrial Ethernet
System Software for S7-300/400 System and Standard Functions - Volume 2/2
A5E00739858-01
23-13
Parameter Data -
Type
Value in Example Description
local_tsap_id ARRAY
[1..16] of
BYTE
local_tsap_id[1] = B#16#E0
local_tsap_id[2] = B#16#03
local_tsap_id[3] = B#16#54
(ASCII equivalent of "T")
local_tsap_id[4] = B#16#43
(ASCII equivalent of "C")
local_tsap_id[5] = B#16#50
(ASCII equivalent of "P")
local_tsap_id[6] = B#16#2D
(ASCII equivalent of "-")
local_tsap_id[7] = B#16#31
(ASCII equivalent of "1")
local_tsap_id[8-16] = irrelevant
Local TSAP-ID: 0xE0035443502D31
rem_staddr ARRAY
[1..6] of
BYTE
"192.168.4.16"
rem_staddr[1] = B#16#C0
(192)
rem_staddr[2] = B#16#A8
(168)
rem_staddr[3] = B#16#04 (4)
rem_staddr[4] = B#16#10 (16)
rem_staddr[5-6] = irrelevant
IP address of the remote connection
transmission point
rem_tsap_id ARRAY
[1..16] of
BYTE
rem_tsap_id[1] = B#16#E0
rem_tsap_id[2] = B#16#04
rem_tsap_id[3] = B#16#54
(ASCII equivalent of "T")
rem_tsap_id[4] = B#16#43
(ASCII equivalent of "C")
rem_tsap_id[5] = B#16#50
(ASCII equivalent of "P")
rem_tsap_id[6] = B#16#2D
(ASCII equivalent of "-")
rem_tsap_id[7] = B#16#31
(ASCII equivalent of "1")
rem_tsap_id[8-16] = irrelevant
Remote TSAP-ID:
0xE0045443502D31
next_staddr ARRAY
[1..6] of
BYTE
next_staddr[1] = B#16#06
next_staddr[2-6] = irrelevant
Rack = 0, slot = 6
(bits 7 to 5: rack no., bits 4 to 0: slot
no.)