The variables dependent on the error code have the following meaning:
Error code Bit Meaning
B#16#01
- OB80_ERROR_INFO:
- OB80_ERR_EV_CLASS:
- OB80_ERR_EV_NUM:
- OB80_OB_PRIORITY:
- OB80_OB_NUM
Cycle time exceeded.
Run time of last scan cycle (ms).
Class of the event that triggered the interrupt.
Number of the event that triggered the interrupt.
Priority class of the OB which was being executed
when the error occurred.
Number of the OB which was being executed when
the error occurred.
B#16#02
- OB80_ERROR_INFO:
- OB80_ERR_EV_CLASS:
- OB80_ERR_EV_NUM:
- OB80_OB_PRIORITY
- OB80_OB_NUM:
The called OB is still being executed.
The respective temporary variable of the called block
which is determined by
OB80_ERR_EV_CLASS and
OB80_ERR_EV_NUM.
Class of the event that triggered the interrupt.
Number of the event that triggered the interrupt.
Priority class of the OB causing the error (for
example: "7" for OB30/Priority class 7 which
should have been started, but could not be
started).
Number of the OB causing the error (for example:
"30" for OB30 which should have been started,
but could not be started).
B#16#05 and
B#16#06
- OB80_ERROR_INFO:
- OB80_ERR_EV_CLASS:
- OB80_ERR_EV_NUM:
- OB80_OB_PRIORITY:
- OB80_OB_NUM:
Bit 0 set:
Bit 7 set:
Bit 8 to 15:
Elapsed time-of-day interrupt due to moving the clock
forward.
Elapsed time-of-day interrupt on return to RUN after
HOLD.
The start time for time-of-day interrupt 0 is in the past.
The start time for time-of-day interrupt 7 is in the past.
Not used
Not used
Not used
Not used
Not used
B#16#07
Meaning of the parameters
see error code B#16#02.
Overflow of OB request buffer for the current priority
class
(Each OB start request for a priority class will be
entered in the corresponding OB request buffer; after
completion of the OB the entry will be deleted. If there
are more OB start requests for a priority class than the
maximum permitted number of entries in the
corresponding OB request buffer, OB80 will be called
with error code B#16#07).
B#16#08
Meaning of the parameters
see error code B#16#02.
Synchronous-cycle interrupt time error
B#16#09
For information on parameters
refer to error code B#16#02.
Interrupt loss due to high interrupt load