Error Information
The following table contains all the error information that is specific to SFB 37 and
can be output via the ERROR and STATUS parameters.
ERROR STATUS(Decimal) Explanation
0 11 Warning: New job not active because the previous job is still busy.
0 25 Communication has started. The job is being processed.
1 1 Communications problems
1 2 Negative acknowledgment, function cannot be executed
1 3 There is no logon for the specified AR_ID.
1 4
Error in the archive data pointer SD_1 involving data length or
data type.
At the first call, the specified AR_ID is outside the permitted
range.
1 5 Requested reset was executed.
1 7 RESET job irrelevant because the current function was
completed or not activated (block in incorrect status).
1 10 Access to local user memory not possible(for example, access to
a deleted DB).
1 12
When the SFB was called:
An instance DB that does not belong to SFB 37 was specified
A shared DB instead of an instance DB was specified
1 18 AR_ID was already being used by an SFB 37.
1 20 Out of working memory.
H-System: SFB called while update in progress
Data Consistency
To ensure data consistency, you may only write to the part of the currently used
sending area only after the current sending process is completed. This is the case
when the status parameters DONE assumes the value 1.