SFBs for Integrated Control
System Software for S7-300/400 System and Standard Functions - Volume 2/2
27-22
A5E00739858-01
Two-Step Control
In two-step control, only the positive pulse output QPOS_P of PULSEGEN is
connected to the on/off actuator. Depending on the manipulated value range being
used, the two-step controller has a bipolar or a unipolar manipulated value range.
Two-Step Control with Bipolar Manipulated Variable Range
(-100% to 100%)
Duration of the pos. pulse
-100.0 %
100.0 %
PER_TM
PER_TM - P_B_TM
P_B_TM
Continuously Off
Continuously On
0.0 %
Two-Step Control with Unipolar Manipulated Variable Range
(0% to 100%)
Duration of the positive pulse
100.0 %
PER_TM
PER_TM - P_B_TM
P_B_TM
0.0 %
The negated output signal is available at QNEG_P if the connection of the two-step
controller in the control loop requires a logically inverted binary signal for the
actuating pulses.
Actuator
Pulse On Off
QPOS_P TRUE FALSE
QNEG_P FALSE TRUE