Manual Mode in Two/Three-Step Control
In the manual mode (MAN_ON = TRUE), the binary outputs of the three-step or
two-step controller can be set using the signals POS_P_ON and NEG_P_ON
regardless of INV.
Control POS_P_ON NEG_P_ON QPOS_P QNEG_P
FALSE FALSE FALSE FALSE
TRUE FALSE TRUE FALSE
FALSE TRUE FALSE TRUE
Three-step control
TRUE TRUE FALSE FALSE
FALSE Any FALSE TRUE Two-step control
TRUE Any TRUE FALSE
Initialization
SFB/FB "PULSGEN" has an initialization routine that is run through when the input
parameter COM_RST = TRUE is set.
All the signal outputs are set to 0.
Error Information
The error output parameter RET_VAL is not used.