Technical data

Table Of Contents
Organization Blocks
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
1-43
OB85_EV_CLASS OB85_FLT_ID Meaning
B#16#39 B#16#B1 I/O access error when updating the process image of the inputs
OB85_DKZ23: ID of the type of process image transfer during
which the I/O access error has occurred
- B#16#10: Byte access
- B#16#20: Word access
- B#16#30: DWord access
- B#16#57: Transmitting a configured consistency range
OB85_Z1: Reserved for internal use by the CPU: logical base
address of the module
If OB85_RESERVED_2 has the value B#16#76, OB85_Z1
receives the return value of the affected SFC (SFC 14, 15, 26
or 27).
OB85_Z23:
- Byte 0: Part process image no.
- Byte 1: Irrelevant, if OB85_DKZ23=B#16#10, 20 or 30;
Length of the consistency range in bytes, if
OB85_DKZ23=B#16#57
- Bytes 2 and 3: The I/O address causing the PAE, if
OB85_DKZ23=B#16#10, 20 or 30;
Logical start address of the consistency range, if
OB85_DKZ23=B#16#57
B#16#39 B#16#B2 I/O access error when transferring the output process image to the
output modules
OB85_DKZ23, OB85_Z1 and OB85_Z23 as for
OB85_FLT_ID=B#16#B1
You obtain the error codes B#16#B1 and B#16#B2 if you have configured the repeated OB85 call of I/O
access errors for the system process image table update.
B#16#39/B#16#38 B#16#B3 I/O access error when updating the process image of the inputs,
incoming/outgoing event
OB85_DKZ23: ID of the type of process image transfer during
which the I/O access error has occurred
- B#16#10: Byte access
- B#16#20: Word access
- B#16#30: DWord access
- B#16#57: Transmitting a configured consistency range
OB85_Z1: Reserved for internal use by the CPU: logical base
address of the module
If OB85_RESERVED_2 has the value B#16#76, OB85_Z1
receives the return value of the affected SFC (SFC 14, 15, 26
or 27).
OB85_Z23:
- Byte 0: Part process image no.
- Byte 1: Irrelevant, if OB85_DKZ23=B#16#10, 20 or 30;
Length of the consistency range in bytes, if
OB85_DKZ23=B#16#57
- Bytes 2 and 3: The I/O address causing the PAE, if
OB85_DKZ23=B#16#10, 20 or 30;
Logical start address of the consistency range, if
OB85_DKZ23=B#16#57