Technical data

Table Of Contents
SFBs for Compact CPUs
System Software for S7-300/400 System and Standard Functions - Volume 2/2
A5E00739858-01
28-15
Basic Parameters:
Here we describe the SFB parameters. They apply to all operating modes. The
parameters specific to the operating mode are described with the individual
operating modes.
Parameter Declaration Data
type
Address
(Instance
DB)
Range of
values
Default Description
LADDR
INPUT WORD 0 CPU specific W#16#0310 The I/O
address of your
submodule,
specified by
you in "HW
Config".
If the E and A
addresses are
not equal, the
lower one of
the two must
be specified.
CHANNEL
INPUT INT 2 0 0 Channel
number:
STOP
INPUT BOOL 4.4 TRUE/FALSE FALSE Stop run
With STOP =
TRUE you can
stop/interrupt
the run
prematurely.
ERR_A
INPUT BOOL 4.5 TRUE/FALSE FALSE Collect
acknowledgme
nt for external
error
External errors
are cleared
acknowledged
with ERR_A =
TRUE.
SPEED
INPUT BOOL 12.0 TRUE/FALSE FALSE Two speed
stages for
Fast/Creep
mode
TRUE = Rapid
mode
FALSE =
Creep mode
WORKING
OUTPUT BOOL 14.0 TRUE/FALSE FALSE Run is in
progress
ACT_POS
OUTPUT DINT 16
-5x10
8
to
5x10
8
pulses
0 Actual position
value
MODE_OUT
OUTPUT INT 20 0, 1, 3, 4, 5 0 Active/configur
ed operating
mode