Technical data

Table Of Contents
SFBs for Compact CPUs
System Software for S7-300/400 System and Standard Functions - Volume 2/2
A5E00739858-01
28-21
Parameters for The Job "Set Reference Point"
Parameter Declaration Data
type
Address
(Instance
DB)
Range of
values
Default Description
SYNC
OUTPUT BOOL 14.3 TRUE/FALSE FALSE Axis is synchronized
Parameters not assigned to the block (Statistical local data):
Parameter Declaration Data
type
Address
(Instance
DB)
Range of
values
Default Description
JOB_REQ
STATIC BOOL 66.0 TRUE/FALSE FALSE Job initialization
(positive edge)
JOB_DONE
STATIC BOOL 66.1 TRUE/FALSE TRUE New job can be
started
JOB_ERR
STATIC BOOL 66.2 TRUE/FALSE FALSE Faulty job
JOB_ID
STATIC INT 68 1, 2 0 Job, 1 = "Set
Reference Point"
JOB_STAT
STATIC
WORD
70 W#16#0000 to
W#16#FFFF
W#16#0000 Job error number
JOB_VAL
STATIC DINT 72
-5x10
8
to
+5x10
8
pulses
0 Job parameter
for reference
point coordinates
Parameters for The Job "Clear Remaining Distance"
Parameters not assigned to the block (Statistical local data):
Parameter Declaration Data
type
Address
(Instance
DB)
Range of
values
Default Description
JOB_REQ
STATIC BOOL 66.0 TRUE/FALSE FALSE Job initialization
(positive edge)
JOB_DONE
STATIC BOOL 66.1 TRUE/FALSE TRUE New job can be
started
JOB_ERR
STATIC BOOL 66.2 TRUE/FALSE FALSE Faulty job
JOB_ID
STATIC IINT 68 1, 2 0 Job, 2 = "Clear
Remaining Distance"
JOB_STAT
STATIC
WORD
70 0 to FFFF hex 0 Job error number
JOB_VAL
STATIC DINT 72 - 0 None.