Technical data

Table Of Contents
Organization Blocks
System Software for S7-300/400 System and Standard Functions - Volume 1/2
1-44
A5E00709327-01
OB85_EV_CLASS OB85_FLT_ID Meaning
B#16#39/B#16#38 B#16#B4 I/O access error when updating the process image of the outputs,
incoming/outgoing event
OB85_DKZ23, OB85_Z1, OB85_Z23 as for
OB85_FLT_ID=B#16#B3
You obtain the error codes B#16#B3 and B#16#B4 if you configured the OB85 call of I/O access errors
entering and outgoing event for process image table updating by the system. After a cold or warm restart,
all access to non-existing inputs and outputs will be reported as I/O access errors during the next process
image table updating.