Technical data

Table Of Contents
SFBs for Compact CPUs
System Software for S7-300/400 System and Standard Functions - Volume 2/2
28-56
A5E00739858-01
Parameter in the SFB for Data Source (Partner CPU)
The table below shows the data types which can be transmitted.
The value for R_OFFSET is determined by the partner CPU.
Source on the partner CPU R_TYP R_NO R_OFFSET (in bytes)
Data block ‘D’ 0 - 255 0 - 510
,
only even values are appropriate
Expanded data block ‘X’: 0 - 255 0 - 510
,
only even values are appropriate
Memory bit ’M’ Irrelevant 0 – 255
Inputs ’E’ Irrelevant 0 – 255
Outputs ’A’ Irrelevant 0 – 255
Counters ‘Z’ Irrelevant 0 – 255
Times ’T Irrelevant 0 – 255
Declarations in the Message Frame
The table below shows the declarations in the message frame header of the
RK512 message frame.
Source on the
partner CPU
to the target, your S7
automation system (local CPU)
Message frame header, bytes
3/4
Instruction
type
5/6 S-DBNR/S
Offset
7/8 Number
in
Data block Data block ED DB/DW Words
Expanded data
block
Data block EX DB/DW Words
Memory bit Data block EM Byte address Bytes
Inputs Data block EI Byte address Bytes
Outputs Data block EO Byte address Bytes
Counters Data block EC Counter number Words
Times Data block ET Timer number Words
Explanation of the abbreviations used:
S-DBNO Source Data Block Number
S Offset Source start address