Technical data

Table Of Contents
SFBs for Compact CPUs
System Software for S7-300/400 System and Standard Functions - Volume 2/2
A5E00739858-01
28-61
Parameters
Note: In this SFB the range of values are all represented in the German memory
conventions.
Parameters Declaration Data type Range of
values
Default Description
SYNC_DB
INPUT INT CPU specific 0 Number of the DB in which
the common data for the
synchronization of the
RK-SFBs are stored
(minimum length = 240
bytes).
EN_R
INPUT BOOL TRUE/FALSE FALSE Control parameter "Enable to
receive"
Job enable
R
INPUT BOOL TRUE/FALSE FALSE Control parameter "Reset".
Job is aborted.
LADDR
INPUT WORD CPU specific W#16#03FF The I/O address of your
submodule, specified by you
in "HW Config".
NDR
OUTPUT BOOL TRUE/FALSE FALSE Status parameter "New Data
Ready" (This parameter is
only set for the duration of
one call):
1. FALSE Job has not been
started or is still being
executed.
2. TRUE Job was executed
successfully.
ERROR
OUTPUT BOOL TRUE/FALSE FALSE Status parameter (This
parameter is only set for the
duration of one call):
Completed job without error