OB86_EV_CLASS OB86_FLT_ID Meaning
B#16#38 B#16#C8 Return of a DP station, however discrepancy in configured and
actual configuration
OB86_MDL_ADDR: Logical base address of the DP master
OB86_Z23: Address of the affected DP slave:
- Bit 0 to 7: No. of the DP station
- Bit 8 to 15: DP master system ID
- Bit 16 to 30: Logical base address of the DP slave
- Bit 31: I/O identifier
B#16#39 B#16#CA PROFINET IO system failure
OB86_MDL_ADDR: logical base address of the IO controller
OB86_Z23:
- Bit 0 to 10: 0 (station number)
- Bit 11 to 14: IO system ID
- Bit 15: 1
- Bit 16 to 31: 0
B#16#39/38 B#16#CB PROFINET IO station failure/station return
OB86_RESERVED_1:
- B#16#C4: no other station is faulty
- B#16#CF: other stations have failed/are faulty
OB86_MDL_ADDR: logical base address of the IO controller
OB86_Z23:
- Bit 0 to 10: Station number
- Bit 11 to 14: IO system ID
- Bit 15: 1
- Bit 16 to 30: Logical base address of the station
- Bit 31: I/O identifier
B#16#39/38 B#16#CC PROFINET IO station faulty/station fault corrected
OB86_RESERVED_1:
- B#16#C4: no other station is faulty
- B#16#CF: other stations have failed/are faulty
OB86_MDL_ADDR: logical base address of the IO controller
OB86_Z23:
- Bit 0 to 10: Station number
- Bit 11 to 14: IO system ID
- Bit 15: 1
- Bit 16 to 30: Logical base address of the station
- Bit 31: I/O identifier
B#16#38 B#16#CD PROFINET IO station return, actual configuration does not march
expected configuration
OB86_MDL_ADDR: logical base address of the IO controller
OB86_Z23:
- Bit 0 to 10: Station number
- Bit 11 to 14: IO system ID
- Bit 15: 1
- Bit 16 to 30: Logical base address of the station
- Bit 31: I/O identifier