28-65
Error in the SFB parameter configuration"
W#16#051D Send/receive job aborted by
Reset of the communication block
Re-assigning parameters
Repeat the call of the communication block.
W#16#0522 A new SEND job was started even
though the previous job has not yet
been completed yet.
Do not start the new SEND job unless the
previous send job is terminated with DONE or
ERROR.
"Error when processing a partner job" only for RK512
Event class
Error code
Event Remedy
W#16#0601 Error in the 1st instruction byte (not 00
or FFH)
Basic header structure error in the partner.
Prove the faulty behavior of the partner device
if required by hooking up an interface tester to
the data link.
W#16#0602 Error in 3rd instruction byte (not A, 0 or
E)
Basic header structure error in the partner.
Prove the faulty behavior of the partner if
required by hooking up an interface tester to
the data link.
W#16#0603 Error in 3rd instruction byte in
subsequent message frames
(instruction not as in the first message
frame)
Basic header structure error in the partner.
Prove the faulty behavior of the partner if
required by hooking up an interface tester to
the data link.
W#16#0604 Error in 4th instruction byte (wrong
instruction character)
Basic header structure error in the partner or
an illegal instruction combination was
requested. Check the permitted instructions.
Prove the faulty behavior of the partner if
required by hooking up an interface tester to
the data link.
W#16#0606 Error in 5th instruction byte (illegal DB
number)
Refer to the job tables for info on permitted
DB numbers, start addresses or lengths.
W#16#0607 Error in 5th or 6th instruction byte (start
address too high)
Refer to the job tables for info on permitted
DB numbers, start addresses or lengths.
W#16#0609 Error in 9th or 10th instruction byte
(coordination memory bit not permitted
for this data type or the bit number is
too high).
Basic header structure error in the partner.
Refer to the job tables for info on when a
coordination memory bit is permitted.
W#16#060A Error in 10th instruction byte (illegal
CPU number)
Basic header structure error in the partner.
"Send error"
Event class
Error code
Event Remedy
W#16#0701
Only for 3964(R):
Sending the first repetition:
An error was detected when
sending the message frame
The partner requested a repetition
with a negative confirmation
character (NCC).
A repetition does not represent an error.
However, it can be an indication of disruptions
on the data link or of a faulty behavior of the
partner. If the message frame is not
transmitted within the maximum number of
repetitions an error number is reported which
describes the error that first occurred.
W#16#0702
Only for 3964(R):
Error while establishing the connection
After STX was transmitted the NCC or
any character (except DLE or STX) was
received.
Prove the faulty behavior of the partner if
required by hooking up an interface tester to
the data link.