Technical data

Table Of Contents
Organization Blocks
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
1-51
The variables dependent on the error code have the following meaning:
Error code Byte/Word Meaning
B#16#D2:
B#16#D3
B#16#D4:
B#16#D5
- OB87_RESERVED_3:
- OB87_RESERVED_4:
Transmission of diagnostic entries currently not
possible.
Synchronization messages cannot be transmitted
(master).
Illegal time-of-day jump due to clock synchronization.
Error when receiving synchronization time (slave).
Contains no further information.
Contains no further information.
B#16#E1:
B#16#E3:
B#16#E4:
- OB87_RESERVED_3:
- OB87_RESERVED_4:
high byte:
low byte:
Incorrect frame ID during global data communication.
Frame length error during global data communication.
Illegal GD packet number received.
interface ID (0: K bus, 1: MPI)
GD circuit number
Contains no further information.
B#16#E2:
- OB87_RESERVED_3:
- OB87_RESERVED_4:
high word:
low word:
GD packet status cannot be entered in the DB
DB number
Contains no further information.
GD circle number (high byte),
GD packet number (low byte)
B#16#E5:
- OB87_RESERVED_3:
- OB87_RESERVED_4:
high word:
low word:
Access error to DB during data exchange via
communication function blocks
Reserved for internal use by CPU.
Number of block containing the MC7 command that
caused the error.
Relative address of the MC7 command that has
caused the error.
The block type may be read from OB_87_RESERVED_1 (B#16#88: OB, B#16#8A:
DB, B#16#8C: FC, B#16#8E: FB).
Error code Meaning
B#16#E6:
- OB87_RESERVED_3:
- OB87_RESERVED_4:
GD group status cannot be entered in DB.
DB number.
Contains no further information.