Technical data

Table Of Contents
System Status Lists (SSL)
System Software for S7-300/400 System and Standard Functions - Volume 2/2
A5E00739858-01
33-19
INDEX = W#16#0008
Name Length Meaning
index 1 word For a standard CPU and the partial list extract W#16#011C:
component ID: W#16#0008
For H CPUs and the partial list extracts W#16#021C and
W#16#031C:
Byte 0: bits 0 to 2: rack no.; bit 3: 0 = reserve CPU, 1 = master
CPU; bits 4 to 7: 1111
Byte 1: component ID: B#16#08
sn_mc/mmc 16 words Serial number of the Memory Card/Micro Memory Card; character string
with a max. length of 32 characters. Shorter names are filled with
B#16#00.
Siemens serial number: only serial number, no index
Product serial number (PSN) of an S7 Micro Memory Card: "MMC"
plus serial number (PSN)
Serial number of an S7 Memory Card: "MC" plus serial number
The character string ends immediately after "MMC" or "MC" if no
Memory Card is installed.
INDEX = W#16#0009
Name Length Meaning
index 1 word For a standard CPU and the partial list extract W#16#011C:
component ID: W#16#0009
For H CPUs and the partial list extracts W#16#021C and
W#16#031C:
Byte 0: bits 0 to 2: rack no.; bit 3: 0 = reserve CPU, 1 =
master CPU; bits 4 to 7: 1111
Byte 1: component ID: B#16#09
manufacturer_id 1 word See PROFIBUS Profile Guidelines Part 1, Identification &
Maintenance Functions
profile_id 1 word See PROFIBUS Profile Guidelines Part 1, Identification &
Maintenance Functions
profile_specific_typ 1 word See PROFIBUS Profile Guidelines Part 1, Identification &
Maintenance Functions
res 13 words Reserved