Technical data

Table Of Contents
System Status Lists (SSL)
System Software for S7-300/400 System and Standard Functions - Volume 2/2
A5E00739858-01
33-31
33.18 Data Record of the Partial List Extract with SSL-ID
W#16#0132 Index W#16#000C
Contents
The partial list extract with SSL ID W#16#0132 and index W#16#000C contains
information about the status of the 32-bit run-time meters 8 … 15 of the module.
Data record
A data record of the partial list extract with SSL ID W#16#0132 and index
W#16#000C has the following structure:
Name Length Meaning
Index 1 word W#16#000C: Time system status
Bszl_0 1 byte Bit x: Status of run-time meter (8+x) , 0 x 7 (Bit = 1: run-time meter is
busy)
Bszl_1 1 byte Reserved
Bszü_0 1 byte Bit x: Overflow of run-time meter (8+x), 0 x 7 (Bit = 1: Overflow)
Bszü_1 1 byte Reserved
Clock 8 2 words Run-time meter 8: time in hours
Clock 9 2 words Run-time meter 9: time in hours
Clock 10 2 words Run-time meter 10: time in hours
Clock 11 2 words Run-time meter 11: time in hours
Clock 12 2 words Run-time meter 12: time in hours
Clock 13 2 words Run-time meter 13: time in hours
Clock 14 2 words Run-time meter 14: time in hours
clock 15 2 words Run-time meter 15: time in hours
Res 1 word Reserved