Technical data

Table Of Contents
System Status Lists (SSL)
System Software for S7-300/400 System and Standard Functions - Volume 2/2
A5E00739858-01
33-45
33.25 SSL-ID W#16#xy91 - Module Status Information
Purpose
If you read the partial list SSL-ID W#16#xy91, you obtain the status information of
modules assigned to the CPU.
Note
An evaluation of the SSL-ID W#16#xy91 is not possible for a submodule with
packed addresses (ET 200S).
Header
The header of partial list SSL-ID W#16#xy91 is structured as follows:
Contents Meaning
SSL-ID The SSL-ID of the partial list extract
W#16#0091 Module status information of all plugged-in modules and
submodules (S7-400 only)
W#16#0191 Status information of all not-deactivated modules/racks with
wrong module identifier (S7-400 only)
W#16#0291 Module status information of all faulty and not-deactivated
modules (S7-400 only)
W#16#0391 Module status information of all unavailable modules (S7-
400 only)
W#16#0591 Module status information of all submodules of the host
module
W#16#0991 Module status information of a DP master system
W#16#0A91 Status information of all DP submodules and DP master
systems (only S7-300 without CPU 318-2 DP) or
PROFINET IO systems
W#16#0C91 Module status information of a module in the central rack or
of an integrated DP interface module or an integrated
PROFINET interface module via the logical base address
W#16#4C91 Module status information of a module connected to an
external DP interface module or an external PROFINET
interface module via the logical base address
If you use more than four external DP interfaces the result
by mistake can be RET_VAL W#16#80A4.
W#16#0D91 Module status information of all modules in the specified
rack/in the specified station (DP or PROFINET)
W#16#0E91 Module status information of all configured modules
(central, distributed, PROFIBUS DP or PROFINET IO