Technical data

Table Of Contents
Organization Blocks
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
1-55
Local Data for OB90
The following table describes the temporary (TEMP) variables of OB90. The
variable names are the default names of OB90.
Variable Data Type Description
OB90_EV_CLASS BYTE Event class and identifiers: B#16#11: active
OB90_STRT_INF BYTE B#16#91: warm restart/cold restart/hot restart
B#16#92: block deleted
B#16#93: downloading OB90 to the CPU in the RUN
mode
B#16#95: termination of the background cycle
OB90_PRIORITY BYTE Priority class: 29 (corresponds to priority 0.29)
OB90_OB_NUMBR BYTE OB number (90)
OB90_RESERVED_1 BYTE Reserved
OB90_RESERVED_2 BYTE Reserved
OB90_RESERVED_3 INT Reserved
OB90_RESERVED_4 INT Reserved
OB90_RESERVED_5 INT Reserved
OB90_DATE_TIME DATE_AND_TIME DATE_AND_TIME of day at which the OB was called