Technical data

Table Of Contents
Organization Blocks
System Software for S7-300/400 System and Standard Functions - Volume 1/2
A5E00709327-01
1-57
Local Data for Startup OBs
The following table describes the temporary (TEMP) variables for a startup OB.
The variable names are the default names of OB100.
Variable Type Description
OB10x_EV_CLASS BYTE Event class and identifiers: B#16#13: active
OB10x_STRTUP BYTE Startup request:
B#16#81: Manual warm restart
B#16#82: Automatic warm restart
B#16#83: Request for manual hot restart
B#16#84: Request for automatic hot restart
B#16#85: Request for manual cold restart
B#16#86: Request for automatic cold restart
B#16#87: Master: Request for manual
cold restart
B#16#88: Master: Request for automatic
cold restart
B#16#8A: Master: Request for manual warm
restart
B#16#8B: Master: Request for automatic warm
restart
B#16#8C: Standby: Request for manual restart
B#16#8D: Standby: Request for automatic
restart
OB10x_PRIORITY BYTE Priority class: 27
OB10x_OB_NUMBR BYTE OB number (100, 101, or 102)
OB10x_RESERVED_1 BYTE Reserved
OB10x_RESERVED_2 BYTE Reserved
OB10x_STOP WORD Number of the event that caused the CPU to stop
OB10x_STRT_INFO DWORD Supplementary information about the current startup
OB10x_DATE_TIME DATE_AND_TIME DATE_AND_TIME of day when the OB was called