Technical data

Table Of Contents
Events
System Software for S7-300/400 System and Standard Functions - Volume 2/2
34-6
A5E00739858-01
Event ID Event OB
W#16#3961 Module/interface module removed, cannot be addressed OB 83
W#16#3863 Module/interface module plugged in, but wrong module type OB 83
W#16#3864 Module/interface module plugged in, but causing problem
(type ID unreadable)
OB 83
W#16#3865 Module plugged in, but error in module parameter assignment OB 83
W#16#3866 Module can be addressed again, load voltage error removed OB 83
W#16#3966 Module cannot be addressed, load voltage error OB 83
W#16#3367 Start of module reconfiguration OB 83
W#16#3267 End of module reconfiguration OB 83
W#16#3968 Module reconfiguration has ended with error OB 83
W#16#3571 Nesting depth too high in nesting levels OB 88
W#16#3572 Nesting depth for Master Control Relays too high OB 88
W#16#3573 Nesting depth too high after synchronous errors OB 88
W#16#3574 Nesting depth for block calls (U stack) too high OB 88
W#16#3575 Nesting depth for block calls (B stack) too high OB 88
W#16#3576 Local data allocation error OB 88
W#16#3578 Unknown instruction OB 88
W#16#357A Jump instruction to target outside of the block OB 88
W#16#3884 Interface module plugged in OB 83
W#16#3984 Interface module removed OB 83
W#16#3981 Interface error entering state OB 84
W#16#3881 Interface error leaving state OB 84
W#16#3582 Memory error detected and corrected by operating system OB 84
W#16#3583 Accumulation of detected and corrected memo errors OB 84
W#16#3585 Error in the PC operating system (only for LC RTX) OB 84
W#16#3986 Performance of an H-Sync link negatively affected OB 84
W#16#3587 Multi-bit memory error detected and corrected OB 84
W#16#35A1 User interface (OB or FRB) not found OB 85
W#16#35A2 OB not loaded (started by SFC or operating system due to
configuration)
OB 85
W#16#35A3 Error when operating system accesses a block OB 85
W#16#35A4 PROFInet Interface DB cannot be addressed OB 85
W#16#34A4 PROFInet Interface DB can be addressed again OB 85
W#16#39B1 I/O access error when updating the process image input table OB 85
W#16#39B2 I/O access error when transferring the process image to the
output modules
OB 85
W#16#39B3/38B3 I/O access error when updating the process image input table OB 85
W#16#39B4/38B4 I/O access error when transferring the process image to the
output modules
OB 85
W#16#38C1 Expansion rack operational again (1 to 21), leaving state OB 86
W#16#39C1 Expansion rack failure (1 to 21), entering state OB 86
W#16#38C2 Expansion rack operational again but mismatch between
setpoint and actual configuration
OB 86
W#16#39C3 Distributed I/Os: master system failure entering state OB 86
W#16#39C4 Distributed I/Os: station failure, entering state OB 86