Technical data

Table Of Contents
Organization Blocks
System Software for S7-300/400 System and Standard Functions - Volume 1/2
1-58
A5E00709327-01
The following table shows the variables OB100_STR_INFO and OB101_STR_INFO.
Bit No. Meaning Possible Binary
Values
Explanation
0000 xxxx Rack number 0 (H CPUs only)
0100 xxxx Rack number 1 (H CPUs only)
1000 xxxx Rack number 2 (H CPUs only)
0001 xxxx Multicomputing (S7-400 only)
0010 xxxx Operation of more than one CPU in the
segmented rack (S7-400 only)
xxxx xxx0 No difference between expected and
actual configuration (S7-300 only)
xxxx xxx1 Difference between expected and
actual configuration (S7-300 only)
xxxx xx0x No difference between expected and
actual configuration
xxxx xx1x Difference between expected and
actual configuration
xxxx x0xx Not an H CPU
xxxx x1xx H CPU
xxxx 0xxx Clock for time stamp not battery-
backed at last POWER ON
31 - 24 Startup information
xxxx 1xxx Clock for time stamp battery-backed at
last POWER ON
0000 0001 Warm restart in multicomputing without
changing setting on the CPU according
to parameter assignment (S7-400 only)
0000 0011 Restart (warm) triggered with mode
selector
0000 0100 Restart (warm) triggered by command
via MPI
0000 0101 Cold restart in multicomputing without
changing setting on the CPU according
to parameter assignment (S7-400 only)
0000 0011 Cold restart triggered with mode
selector
0000 1000 Cold restart triggered by command via
MPI
0000 1010 Hot restart in multicomputing without
changing setting on the CPU according
to parameter assignment (S7-400 only)
0000 1011 Hot restart triggered with mode
selector (S7-400 only)
0000 1100 Hot restart triggered by command via
MPI (S7-400 only)
0001 0000 Automatic restart (warm) after battery-
backed POWER ON
23 - 16 Startup just completed
0001 0001 Cold restart after battery-backed
POWER ON according to parameter
assignment