Event ID Event
W#16#494E STOP caused by power failure
W#16#494F STOP caused by configuration error
W#16#4550 DEFECTIVE: internal system error
W#16#4555 No restart possible, monitoring time elapsed
W#16#4556 STOP: memory reset request from communication system / due to data inconsistency
W#16#4357 Module watchdog started
W#16#4358 All modules are ready for operation
W#16#4959 One or more modules not ready for operation
W#16#4562 STOP caused by programming error (OB not loaded or not possible
W#16#4563 STOP caused by I/O access error (OB not loaded or not possible
W#16#4567 STOP caused by H event
W#16#4568 STOP caused by time error (OB not loaded or not possible)
W#16#456A STOP caused by diagnostic interrupt (OB not loaded or not possible)
W#16#456B STOP caused by removing/inserting module (OB not loaded or not
possible)
W#16#456C STOP caused by CPU hardware error (OB not loaded or not possible,
or no FRB)STOP
W#16#456D STOP caused by program sequence error (OB not loaded or not
possible)
W#16#456E STOP caused by communication error (OB not loaded or not possible)
W#16#456F STOP caused by rack failure OB (OB not loaded or not possible)
W#16#4570 STOP caused by process interrupt (OB not loaded or not possible)
W#16#4571 STOP caused by nesting stack error
W#16#4572 STOP caused by master control relay stack error
W#16#4573 STOP caused by exceeding the nesting depth for synchronous errors
W#16#4574 STOP caused by exceeding interrupt stack nesting depth in the
priority class stack
W#16#4575 STOP caused by exceeding block stack nesting depth in the priority
class stack
W#16#4576 STOP caused by error when allocating the local data
W#16#4578 STOP caused by unknown opcode
W#16#457A STOP caused by code length error
W#16#457B STOP caused by DB not being loaded on on-board I/Os
W#16#497C STOP caused by integrated technology
W#16#457D Reset/clear request because the version of the internal interface to the integrated
technology was changed.
W#16#457F STOP caused by STOP command
W#16#4580 STOP: back-up buffer contents inconsistent (no transition to RUN)
W#16#4590 STOP caused by overloading the internal functions
W#16#49A0 STOP caused by parameter assignment error or non-permissible
variation of setpoint and actual extension: Start-up blocked.
W#16#49A1 STOP caused by parameter assignment error: memory reset request
W#16#49A2 STOP caused by error in parameter modification: startup disabled
W#16#49A3 STOP caused by error in parameter modification: memory reset
request
W#16#49A4 STOP: inconsistency in configuration data
W#16#49A5 STOP: distributed I/Os: inconsistency in the loaded configuration
information
W#16#49A6 STOP: distributed I/Os: invalid configuration information
W#16#49A7 STOP: distributed I/Os: no configuration information
W#16#49A8 STOP: error indicated by the interface module for the distributed I/Os